Mechanism and Effect of DC Charge Accumulation on SF6 Gas Insulated Spacers
Mechanism and Effect of DC Charge Accumulation on SF6 Gas Insulated Spacers
复制标题
DOI:
10.1109/mper.1989.4310816
复制
发表时间:
1989-07
期刊:
影响因子:
--
通讯作者:
H. Fujinami;T. Takuma;M. Yashima;T. Kawamoto
中科院分区:
文献类型:
--
作者:
H. Fujinami;T. Takuma;M. Yashima;T. Kawamoto
Mechanism and effect of DC charge accumulation on the surface of a solid insulating support (spacer) have been studied in compressed SF/sub 6/ gas using various cylindrical model spacers. The distribution of surface charged is closely related to the normal component (gas side) E/sub n/ of electric field on the spacer surface. The ,maximum charge density can be estimated from the condition of E/sub n/=0. When voltage is applied in a polarity opposite to prestressed DC, surface charge increases the maximum field strength in the arrangement, resulting in the reduction of the insulating ability. It is possible to estimate the lowest flashover voltage due to surface charges only from numerical fields calculations. An anticharging spacer shaped along electric lines of force is proposed and studied. >