Mechanism and Effect of DC Charge Accumulation on SF6 Gas Insulated Spacers

Mechanism and Effect of DC Charge Accumulation on SF6 Gas Insulated Spacers
复制标题

DOI:
10.1109/mper.1989.4310816
复制
发表时间:
1989-07
期刊:
IEEE Power Engineering Review
影响因子:
--
通讯作者:
H. Fujinami;T. Takuma;M. Yashima;T. Kawamoto
H. Fujinami;T. Takuma;M. Yashima;T. Kawamoto
中科院分区:
其他
文献类型:
--
作者:
H. Fujinami;T. Takuma;M. Yashima;T. Kawamoto

文献摘要

被引文献

相似文献

在压缩的SF/SUB 6/GAS中,用不同的圆柱模型间隔棒研究了固体绝缘支撑体(垫片)表面直流电荷积累的机理和效果。表面带电分布与隔离体表面电场的法向分量(气体侧)E/subn/密切相关。最大电荷密度可以从E/subn=0的条件中估计出来。当电压施加在与预应力直流相反的极性时,表面电荷增加了排列中的最大场强,导致绝缘能力降低。仅通过数值场计算就可以估计由于表面电荷引起的最低闪络电压。提出并研究了一种沿电力线形状的反带电间隔器。>
Mechanism and effect of DC charge accumulation on the surface of a solid insulating support (spacer) have been studied in compressed SF/sub 6/ gas using various cylindrical model spacers. The distribution of surface charged is closely related to the normal component (gas side) E/sub n/ of electric field on the spacer surface. The ,maximum charge density can be estimated from the condition of E/sub n/=0. When voltage is applied in a polarity opposite to prestressed DC, surface charge increases the maximum field strength in the arrangement, resulting in the reduction of the insulating ability. It is possible to estimate the lowest flashover voltage due to surface charges only from numerical fields calculations. An anticharging spacer shaped along electric lines of force is proposed and studied. >