This paper analyzes the Sampled Value (SV) Process Bus concept that was recently introduced by the IEC 61850-9-2 standard. This standard proposes that the Current and Voltage Transformer (CT, PT) outputs that are presently hard wired to various devices (relays, meters, IED, and SCADA) be digitized at the source and then communicated to those devices using an Ethernet-Based Local Area Network (LAN). The approach is especially interesting for modern optical CT/PT devices that possess high quality information about the primary voltage/current waveforms, but are often forced to degrade output signal accuracy in order to meet traditional analog interface requirements (5 A/120 V). While very promising, the SV-based process bus brings along a distinct set of issues regarding the overall reliability of the new Ethernet communications-based protection and control system. This paper looks at the Merging Unit Concept, analyzes the protection system reliability in the process bus environment, and proposes an alternate approach that can be used to successfully deploy this technology. Multiple scenarios used with the associated equipment configurations are compared. Additional issues that need to be addressed by various standards bodies and interoperability challenges posed by the SV process bus LAN on real-time monitoring and control applications (substation HMI, SCADA, engineering access) are also identified.