Couplings in Phase Domain Impedance Modeling of Grid-Connected Converters
Couplings in Phase Domain Impedance Modeling of Grid-Connected Converters
复制标题
DOI:
10.1109/tpel.2016.2542244
复制
发表时间:
2016-03
影响因子:
6.7
通讯作者:
Mohammad Kazem Bakhshizadeh;Xiongfei Wang;F. Blaabjerg;J. Hjerrild;L. Kocewiak;C. Bak;Bo Hesselbak
中科院分区:
文献类型:
--
作者:
Mohammad Kazem Bakhshizadeh;Xiongfei Wang;F. Blaabjerg;J. Hjerrild;L. Kocewiak;C. Bak;Bo Hesselbak
The output impedance of a power converter plays an important role in the stability assessment of the converter. The impedance can be expressed in different frames such as the stationary frame (phase domain) or in the synchronous frame (dq domain). To treat the three-phase system like a single-phase system, the system can be divided into positive and negative sequences in the phase domain. This paper demonstrates that there exist couplings between the positive and negative sequences, even in a balanced system due to the PLL, which is important for synchronization. Further it will be shown that even though these couplings are very small in magnitude, they are important in the stability of the converter.