High Impedance Fault Area Location in Distribution Systems Based on Current Zero Sequence Component

High Impedance Fault Area Location in Distribution Systems Based on Current Zero Sequence Component
复制标题

DOI:
10.1109/tla.2016.7437220
复制
发表时间:
2016-03
影响因子:
1.3
通讯作者:
João Tito Almeida Vianna;L. Araujo;D. Penido
João Tito Almeida Vianna;L. Araujo;D. Penido
中科院分区:
工程技术4区
文献类型:
--
作者:
João Tito Almeida Vianna;L. Araujo;D. Penido

文献摘要

被引文献

相似文献

本文提出了一种新的方法检测和区域定位的高阻抗故障(HIF)的不平衡配电系统。该方法被称为准差动零序保护(PQDSZ),它通过分析配电馈线上的电流零序有效值来检测这些故障。检测依赖于由两个测量点定义的差分区域。数据被发送到控制中心,控制中心分析接收到的电流之间的关系,并在检测到任何问题时发出警报。为了验证PQDSZ的有效性,给出了一个RTDS和真实的自动化设备的仿真系统。
This paper presents a new methodology for detection and area location of high impedance faults (HIF) on unbalanced distribution systems. The method is called Quasi-Differential Zero Sequence Protection (PQDSZ) and it detects these faults by analyzing the current zero sequence rms value on a distribution feeder. The detection relies on a differential area, defined by two points of measurement. The data is sent to a control center, which analyzes the relation between the received currents and send an alarm if any problem is detected. A simulation system with the RTDS and real automation equipment is presented, in order to validate the PQDSZ.