Experimental evaluation of a UHV tower model for lightning surge analysis
Experimental evaluation of a UHV tower model for lightning surge analysis
复制标题
DOI:
10.1109/61.368374
复制
发表时间:
1995
影响因子:
4.4
通讯作者:
Takeshi Yamada;A. Mochizuki;J. Sawada;E. Zaima;T. Kawamura;A. Ametani;M. Ishii;S. Kato
中科院分区:
文献类型:
--
作者:
Takeshi Yamada;A. Mochizuki;J. Sawada;E. Zaima;T. Kawamura;A. Ametani;M. Ishii;S. Kato
An experimental investigation was performed on a UHV tower model for the EMTP multiconductor calculation of lightning overvoltage at substations associated with back-flashover at an adjacent transmission tower. The various lightning surge response characteristics were measured on an actual UHV tower, and parameters of a multistory transmission tower model that can reproduce voltages across the insulator strings, voltages of the crossarms, and voltages of the power lines were determined. A value of 120 /spl Omega/ was determined as the surge impedance at each section of the multistory tower model, which closely agreed with the tower surge impedance measured for the UHV tower alone. >