A new control method of suppressing DC-capacitor voltage ripples caused by third-order harmonic compensation in three-phase active power filters
A new control method of suppressing DC-capacitor voltage ripples caused by third-order harmonic compensation in three-phase active power filters
复制标题
DOI:
10.1109/ecce.2016.7854713
复制
发表时间:
2016-09
期刊:
影响因子:
--
通讯作者:
Tomoyuki Mannen;Issei Fukasawa;H. Fujita
中科院分区:
文献类型:
--
作者:
Tomoyuki Mannen;Issei Fukasawa;H. Fujita
This paper proposes a new control method suitable for active power filters to reduce the dc capacitor voltage ripples associated with the third-order harmonic current compensation. The proposed method superimposes a negative-sequence fundamental current on the compensating current to cancel out the active power ripple caused by the third-order harmonic current. As a result, the proposed method has the capability to eliminate the dc capacitor voltage ripple at double the source frequency. Experimental results obtained by a 10-kW three-phase diode rectifier verify the validity of the proposed method. The proposed method exhibits a good suppression performance of the dc capacitor voltage ripple at double the source frequency.