Lightning impulse voltage and overshoot evaluation proposed in drafts of IEC 60060-1 and future UHV testing
Lightning impulse voltage and overshoot evaluation proposed in drafts of IEC 60060-1 and future UHV testing
复制标题
IEC 60060-1草案和未来特高压测试中提出的雷电冲击电压和过冲评估
DOI:
10.1109/tdei.2010.5595567
复制
发表时间:
2010
影响因子:
3.1
通讯作者:
E. Gockenbach
中科院分区:
文献类型:
--
作者:
M. Hinow;W. Hauschild;E. Gockenbach
Lightning impulse (LI) voltage testing is an indispensable method for quality assurance of high voltage (HV) and ultra high voltage (UHV) insulation. Not avoidable parasite inductances of the testing circuit provide an oscillation, known as overshoot, at the peak of the lightning impulse (LI). The present paper gives an overview of existing and proposed overshoot evaluation methods of LI voltage. An analytic derivation clarifies the relation between an overshoot magnitude- and overshoot magnitude-/duration- considering method. Hence the finding is derived that both methods provide similar results by applying power transformer testing. Moreover the current paper identifies that a higher permitted overshoot is required for UHV testing by keeping the front time of T1=1.2 μs.