Heat transfer and pressure drop correlations for the wavy fin and flat tube heat exchangers

Heat transfer and pressure drop correlations for the wavy fin and flat tube heat exchangers
复制标题

DOI:
10.1016/j.applthermaleng.2006.11.012
复制
发表时间:
2007-08
影响因子:
6.4
通讯作者:
Dong Junqi;Jiangpin Chen;Zhi-jiu Chen;Zhou Yimin;Wenfeng Zhang
Dong Junqi;Jiangpin Chen;Zhi-jiu Chen;Zhou Yimin;Wenfeng Zhang
中科院分区:
工程技术2区
文献类型:
--
作者:
Dong Junqi;Jiangpin Chen;Zhi-jiu Chen;Zhou Yimin;Wenfeng Zhang

文献摘要

被引文献

相似文献

对11台波纹翅片扁管叉流换热器进行了实验研究。在空气侧雷诺数为800-6500的范围内,以2.5m3/h的管程水流量为条件,对不同的翅片间距、长度和高度进行了一系列试验。采用有效性-NTU法对空气侧热性能数据进行了分析。采用科尔本j因子和范宁摩擦因子f作为Re的函数,研究了不同几何参数下的换热和压降特性。考察了翅片间距、翅片高度和翅片长度对换热和压降性能的影响。通过多元线性回归分析和F检验,得出j和f因子的一般相关。j和f因子的相关性可以预测95%的实验数据,误差在± 10%以内。
A total of 11 cross-flow heat exchangers having wavy fin and flat tube were studied experimentally. A series of tests were conducted for air side Reynolds number in the range of 800–6500 with different fin pitches, fin lengths and fin heights, at a constant tube-side water flow rate of 2.5m3/h. The air side thermal performance data were analyzed using the effectiveness-NTU method. The characteristics of heat transfer and pressure drop for different geometry parameters were reported in terms of Colburn j-factor and Fanning friction factor f, as a function of Re. The effects of fin pitch, fin height and fin length on the performance of heat transfer and pressure drop were examined. The general correlations for j and f factors were derived by multiple linear regression analysis and F test of significance. The correlations for j and f factors can predict 95% of the experimental data within ±10%.