Dynamic Modeling of Three-Phase Asymmetric Power Transformers With Magnetic Hysteresis: No-Load and Inrush Conditions
Dynamic Modeling of Three-Phase Asymmetric Power Transformers With Magnetic Hysteresis: No-Load and Inrush Conditions
复制标题
DOI:
10.1109/tec.2010.2065231
复制
发表时间:
2010-09
影响因子:
4.9
通讯作者:
P. Moses;M. Masoum;H. Toliyat
中科院分区:
文献类型:
--
作者:
P. Moses;M. Masoum;H. Toliyat
A new dynamic model of a three-phase three-leg transformer for steady-state and transient operating conditions is proposed in this paper. With very few exceptions, the existing models oversimplify the magnetic interactions in multileg core topologies and employ single-value nonlinear functions for modeling core nonlinearities. Unfortunately, this does not provide sufficient accuracy for a wide range of dynamic disturbances such as dc bias, ferroresonance, and inrush. For this purpose, a new time-domain model based on magnetic-circuit theory is developed to include dynamic-hysteresis behavior (major and minor loops) in asymmetric three-leg core topologies. Furthermore, a new analysis is performed to study the impacts of hysteresis on no-load and transient inrush current behavior in three-phase transformers. Simulation results have been successfully compared with measurements to verify the accuracy of the proposed model.