文献摘要

被引文献

相似文献

In the radiant ceiling and outdoor air system,part of sensible load would be dealed with the radiant ceiling,the remaining sensible load and the entire latent load would be dealed with the outdoor air.Hence,for the purpose of dehumidification,the cold water with low temperature should be provided to the outdoor air unit,while the cold water with relatively higher temperature should be provided to the radiant ceiling to avoid moisture condensation.However,for most of chiller units,the standard supply/return water temperatures are 7 ℃/12 ℃,respectively.In this paper,taking the chiller unit as cold source,the form of system was firstly analyzed.This is followed by the presentation of a new developed system which could provide cold water with different temperatures to the radiant ceiling and outdoor air system.In addition,the control strategy of this system was discussed.Finally,taking a real house as an example,the energy consumption for this system was calculated.