Study on Immunity of Distributed Generation System linked to Power System for Voltage Sags
Study on Immunity of Distributed Generation System linked to Power System for Voltage Sags
批准号:
18560292
负责人:
IYODA Isao
金额:
$2.41万
依托单位国家:
日本
项目类别:
Grant-in-Aid for Scientific Research (C)
财政年份:
2006
资助国家:
日本
项目状态:
已结题
起止时间:
2006 至 2007
中文摘要
分布式电源的接入为解决环境问题提供了一种很有希望的对策,但其在电压跌落时的不当运行可能会给整个电力系统带来严重的问题。本研究的目的是调查在日本占有最大的光伏发电系统(PV-system)对电压跌落的抗扰性。根据提出的研究计划,制备了小型磁接触器和包含逆变器的规模化光伏系统,并对电磁接触器和逆变器与电力系统的连接进行了大量的实验研究。结果:1。接触器的开度受跌落开始时系统电压相位角的影响,本研究中跌落发生后的接触器开度时间为10ms ~ 65ms。明确了接触器开断时间偏差的原因是由于电压跌落时电压相位角的偏差引起的电压跌落时磁激励电流的偏差。发现部分电压骤降引起的接触器开路时间比完全电压骤降引起的接触器开路时间短。在最短的情况下,光伏逆变器可能在故障开始时间16ms后停止运行。停止的原因不是控制系统的误操作,而是经济产业省(METI)发布的指导方针中推荐的保护方案,以防止停电时光伏系统的独立运行,以避免配电线路的意外上电。研究了通过修改保护方案来解决这一问题。本研究结果对于提高DSs对电压跌落的抗跌性,对最大限度地利用可再生能源具有一定的参考价值。
英文摘要
Distributed generations (DS) connected to power system increases a promising countermeasure for the environmental issue, and their inappropriate operation for voltage sags might cause a serious problems for entire power system. The aim of this study is to investigate the immunity of photo voltaic power generation system (PV-system) that shares largest part of DSs in Japan, for voltage sags. Small magnetic contactors and a scaled PV-system including inverter are prepared and plenty of experimental studies were carried out for electro-magnetic contactors and the inverter linked to power system, following proposed study plan. Results are:1. The open of contactor is affected by the phase angle of the system voltage at the starting time of the sag, the contactor open time after the occurrence of sag varies 10ms to 65ms in this study. The reason of the deviation of the contactor open time is clarified as the deviation of the magnetic excitation current during the voltage sag caused by the deviation of the voltage phase angle at the starting time of the sag. A phenomenon that contactor open time caused by partial voltage sag is shorter than that of complete voltage sag case has been found.2. PV-system Inverter might stop its operation 16ms after the starting time of the sag as the shortest case. The reason of the stop is not the maloperation of the control system, but the protection scheme recommended in the guideline issued by the Ministry of Economy, Trade and Industry (METI), to prevent the stand-alone operation of the PV-system during blackout to avoid the unexpected energization of distribution lines. The solution for this problem by revising the protection scheme has been studied.The results acquired by this study are worth for improvement of immunity of DSs for voltage sags, and effective for the maximum utilization of renewable energy.
期刊论文(0)
专著(0)
科研奖励(0)
会议论文
瞬低に対する電磁接触器の応答の実験的考察
电磁接触器对电压暂降响应的实验考虑
DOI:
--
发表时间:
2007
期刊:
影响因子:
--
作者:
[(Isao IYODA), Masaya HIRATA, Nobuyuki SHIGEI, Sompathana POUNYAKHET, Kenji OTA, Toshifumi ISE, Isao IYODA, 伊与田 功]
通讯作者:
伊与田 功
Affect of Voltage Sags on Electro-magnetic Contactor
电压暂降对电磁接触器的影响
DOI:
--
发表时间:
期刊:
9^t^h International ConferenceElectric Power Quality and Utilization (投稿中)
影响因子:
--
作者:
[(Isao IYODA), Masaya HIRATA, Nobuyuki SHIGEI, Sompathana POUNYAKHET, Kenji OTA, Toshifumi ISE]
通讯作者:
Toshifumi ISE
Detailed Study on Operability of Inverters for Distributed Generation during Voltage Sags and Improvement of Function for Power Quality
-
批准号:20560284
-
项目类别:Grant-in-Aid for Scientific Research (C)
-
资助金额:$3.0万
-
财政年份:2008
-
负责人:IYODA Isao
-
依托单位:
海外基金